Where does a leader attach? A 3D electrogeometric model
The line is the T20–T21 valley span (645.6 m) from the middle-phase vulnerability paper, on real terrain from three surface models. Leaders come down at an angle drawn from g(ψ) = (2/π)·cos²ψ and attach to the first object they come within striking distance of: a shield wire, a phase or the ground. Change the current, the terrain, the polarity and the angle, and watch where the stroke ends. New to leaders? See the mechanism step by step first.
Storm: many leaders at once
Leaders land at random positions and angles; currents come from the distribution.Cross-section at u = 0.75
view along the line, C1 (SW) on the rightAlong the span
click to move the sectionHow lightning finds a transmission line
Each step sets up the 3D scene and fires a leader. Read the note, then change one control and fire again. The physics behind each stage (stepped leader, upward leaders, final jump, return stroke) is animated in 2D on the Leader mechanism page.
Model and equations (paper, Section II)
(1) Striking distances, I in kA, r in m
(2) Leader-angle distribution and exposure width
(3) Middle phase beneath the top phase
(4) Ground capture surface
(5)(6) Exposed height and maximum attachable current
(7) Critical flashover current
(8) Flashover-capable attachments, one side of the span
(9) Reach of an S arrester at one tower
What the 3D scene adds
Leaders are traced as straight lines in the plane across the line, as in the paper's numerical model. The jagged channel, branches, connecting leader and cloud are drawing only. A storm samples ψ with density ∝ cos ψ and a uniform offset, which reproduces the horizontal-equivalent weighting of (2). Its exposure width therefore converges to the closed form. Heights are to scale; the cloud is not (real charge centres sit 5–8 km up). The model is two-dimensional per section. It ignores upward-leader competition, conductor swing and 3D terrain, and positive leaders use the same striking distances as negative ones.