Strike & shielding · 3D Strike Lab

Where does a leader attach? A 3D electrogeometric model

The line is the T20–T21 valley span (645.6 m) from the middle-phase vulnerability paper, on real terrain from three surface models. Leaders come down at an angle drawn from g(ψ) = (2/π)·cos²ψ and attach to the first object they come within striking distance of: a shield wire, a phase or the ground. Change the current, the terrain, the polarity and the angle, and watch where the stroke ends. New to leaders? See the mechanism step by step first.

Ready. Press Fire leader, or try a lesson below.
Loading 3D engine…
shield wirephase R / Tphase S, red where exposedground capture surface GR/T arresterS arrester+ / − chargedrag to orbit · scroll to zoom · right-drag to pan

Storm: many leaders at once

Leaders land at random positions and angles; currents come from the distribution.

Cross-section at u = 0.75

view along the line, C1 (SW) on the right
rc shield wirerc R / Trc S, exposed height eG (rg above ground)leader path

Along the span

click to move the section
C1 (SW)C2 (NE)Ic flashover currentsection
Guided tour

How lightning finds a transmission line

Each step sets up the 3D scene and fires a leader. Read the note, then change one control and fire again. The physics behind each stage (stepped leader, upward leaders, final jump, return stroke) is animated in 2D on the Leader mechanism page.

Model and equations (paper, Section II)

(1) Striking distances, I in kA, r in m

Love: rc = rg = 10·I^0.65  ·  Brown–Whitehead: rc = 7.1·I^0.75, rg = 6.4·I^0.75

(2) Leader-angle distribution and exposure width

WS(x, I) = ∫ W⊥(x, I, ψ) · g(ψ) / cos ψ dψ,   g(ψ) = (2/π)·cos²ψ,   |ψ| ≤ 87.5°

(3) Middle phase beneath the top phase

W⊥ = e·sin ψ  →  WS = (e/π)·sin²ψm ≈ e/π;   fully exposed: d/π = 1.50 m for d = 4.7 m

(4) Ground capture surface

G(xw, I) = maxξ { z(ξ) + [rg² − (xw − ξ)²]^½ },   xw = xS + rc

(5)(6) Exposed height and maximum attachable current

e = min{ d, max[0, yS + d/2 − G] }  ·  level ground: Imax = [(hS + d/2)/Ag]^(1/b)  ·  heff = yS − (G − rg)

(7) Critical flashover current

Ic = 2·Uref / (k·Zc),   k = Zch / (Zch + Zc/2)  → 912.5 kV, 535 Ω, 400 Ω: k = 0.60, Ic ≈ 5.7 kA

(8) Flashover-capable attachments, one side of the span

NS ≈ 10⁻⁶·Ng·(d/π)·∫₀ᴸ [P(Imax(x)) − P(Ic)]⁺ dx

(9) Reach of an S arrester at one tower

xp = c·(τf − τg)/2 ≈ 60–90 m (c = 300 m/µs)

What the 3D scene adds

Leaders are traced as straight lines in the plane across the line, as in the paper's numerical model. The jagged channel, branches, connecting leader and cloud are drawing only. A storm samples ψ with density ∝ cos ψ and a uniform offset, which reproduces the horizontal-equivalent weighting of (2). Its exposure width therefore converges to the closed form. Heights are to scale; the cloud is not (real charge centres sit 5–8 km up). The model is two-dimensional per section. It ignores upward-leader competition, conductor swing and 3D terrain, and positive leaders use the same striking distances as negative ones.