Strike & shielding · Leader mechanism

How a lightning leader finds the line

Before any current flows, a channel of charged air has to grow from the cloud to the ground. That channel, the leader, decides where the lightning strikes. This page follows one flash in nine steps, from the charge in the cloud to the return stroke. It ends with the simple rule the electrogeometric model uses in place of all this physics: the striking distance.

Step 1 of 9

Striking distance

grows with the current

Leader angle distribution

g(ψ) = (2/π)·cos²ψ

How common is that current?

first negative strokes
From physics to a design rule

What the electrogeometric model keeps, and what it drops

Keeps: the reach grows with the current

A leader that will carry a large current holds more charge and launches the final jump from further away. The EGM turns this into one number, r(I), drawn as an arc around every conductor. A shield wire that wins for 30 kA may lose a weak 5 kA stroke to a phase conductor.

Keeps: first object within reach wins

Upward leaders race each other, and the one that meets the downward leader first takes the stroke. The EGM replaces the race by geometry: follow the leader down and see whose arc it crosses first. The ground takes part with its own distance rg.

Drops: the leader is not always vertical

The classical EGM brings every leader straight down. Real leaders arrive at an angle. Then the side of the line is open, and a middle phase directly below the top phase can be reached. That is the paper's leader-angle model, and the right-hand column of the EGM calculator.

Drops: upward-leader physics

The EGM ignores how long upward leaders grow, how fast, and from which point. Leader progression models (CIGRE, Rizk, Dellera–Garbagnati) treat this in detail. They are more accurate for tall structures but need more inputs. For a 46 m tower the EGM is the accepted engineering tool.

Drops: terrain, in 2D

The arcs here stand over level ground. Over a valley the ground capture surface falls away, and more of the phases is exposed. The 3D Strike Lab shows this on the T20–T21 span.

Next: what the current does

Once attached, the current is a source. On a shield wire it lifts the tower (Backflashover Lab). On a phase it sends surges along the line (Relief Wave Lab). The Stroke current page shows its shape.

Numbers and formulas used on this page

Striking distance

Love / CIGRE: r = 10·I0.65 to conductors and ground. Brown–Whitehead: rc = 7.1·I0.75 to conductors, rg = 6.4·I0.75 to ground (I in kA, r in m).

Leader angle

g(ψ) = (2/π)·cos²ψ per unit horizontal width, |ψ| ≤ 87.5°. Sampled as sin ψ uniform with the perpendicular offset uniform, as in the 3D Strike Lab.

Geometry

T20 cross-section at the tower: shield wires at ±3.2 m, 46.0 m; phases R, S, T at ±4.5 m, 43.1, 38.4 and 33.7 m; level ground.

Typical values in the text

Stepped leader: steps of 10–200 m (typically about 50 m), 20–50 µs apart, average speed about 2·10⁵ m/s, about 5 C lowered in some tens of milliseconds. Return stroke: one third to one half of the speed of light. Dart leader: about 10⁷ m/s. Interstroke interval: some tens of milliseconds, typically 3–5 strokes per negative flash. Ranges after Rakov & Uman, Lightning: Physics and Effects, and CIGRE TB 549.

Current distribution

CIGRE TB 63 two-part log-normal for first negative strokes (median about 31 kA). Indonesian measurements give lower medians, 22–24 kA.