Why an insulator flashes, or does not
Each phase hangs on a string of 12 glass discs with arcing horns. In a lightning surge the discs do not matter much: the flashover runs through the air between the horns. It is not instant. Above a critical field a leader grows from the horns across the gap, and it needs time to bridge it. A short, high pulse can pass without a flashover, while a lower but longer one may not.
Across the horn gap
leader length to scaleVoltage and the strength of the remaining gap
kVLeader length
cm, of 144 cmHigher voltage, faster flashover; shorter tail, higher strength
Each curve is the same insulator under one wave shape. A point is the peak voltage and the time at which the leader bridges the gap. The left end of each curve is its critical peak: below it, the wave ends before the leader can finish.
Critical peak by wave shape
| Wave | Leader model | CIGRE short-tail |
|---|
CIGRE short-tail column: CFONS = (0.977 + 2.82/τ)·CFO with CFO = 912.5 kV and τ the tail time constant, the formula the Compare Lab and the grounding modules use. Both agree that short tails need a higher peak. The simple formula climbs much faster for tails below about 6 µs, where it is outside its intended range.
Six lessons
Below 913 kV nothing grows
The leader advances only while the voltage exceeds E₀ times the remaining gap. At the start that is 634 kV/m × 1.44 m = 913 kV. Any voltage below it can last as long as it likes. This is why the paper's calibration says the string "withstands 912.47 kV and flashes at 912.56 kV" on a long wave.
A peak is not a flashover
Once started, the leader shortens the gap, the field at its tip rises, and it accelerates. But it needs a microsecond or more. In the paper's −69 kA backflashover case, phase S saw 1.04 MV and the leader grew only 6.2 cm before the voltage fell. A fixed-CFO check would have called it a flashover.
Short tails are easier to withstand
In a backflashover the footing and the adjacent towers send relief waves within 0.4–4 µs, so the insulator sees a short-tailed pulse. That is why designs use a "non-standard" CFONS above the standard CFO.
The time to flashover is the arrester's window
An arrester only helps if its gap sparks over and its relief wave arrives before the leader finishes. For a 10 kA direct strike the far insulator takes about 0.7–0.9 µs after the surge arrives. That gives the 60–90 m reach of a single arrester in the Relief Wave Lab.
884 kV or 912.5 kV?
884 kV is the specification CFO: a 50% flashover voltage for the standard wave, a statistical figure. 912.5 kV is the deterministic calibration of the leader model in EMTP. They differ by 3%. The screening pages use 884 kV with the CIGRE formula; the travelling-wave labs use the leader model.
The arrester gap is the weaker link, on purpose
The arrester's series gap (650 ± 50 mm) sparks over at about 570 kV, well below the horn gap. On a protected phase the gap always goes first and the insulator is spared. No volt–time curve is published for the gap, so the paper uses a fixed 570 kV and tests 450 and 500 kV.
Model behind the page
Leader progression
Wave shapes
Leader progression is a deterministic model of the 50% behaviour. Real flashover voltages scatter by a few percent (standard deviation about 3% for the CFO).