How much lightning does the line see?
Every design number on this site starts from two inputs: how often lightning strikes the ground near the line, and how strong the strokes are. Here is what the lightning-location system recorded around the SBSLM–SGKIL line from May 2019 to June 2026, and how it compares with the standard assumptions.
Where the strokes fell
local km, north up, zoomed to the recorded strokes · click a towerPeak current
recorded strokes against standard distributionsStrokes per year
Along the line: strokes within 1 km and lightning faults 2022–2025
towers 1–118Five lessons
A hotspot, not an average
The line-average ground flash density is about 4 flashes/km²/yr, but around T19–T28 it reaches 12–13. Every rate on this site uses the local value of each tower. A design based on the average would underestimate this section threefold.
Weaker strokes than the textbook
The median recorded peak is 22 kA against 31 kA in the CIGRE distribution. More weak strokes means more strokes inside the 5.7–17 kA window that can reach phase S, and fewer above the backflashover threshold.
The record misses what matters most
Detection efficiency is lowest for weak strokes, exactly those that cause shielding failures. A 10 kA stroke missing from the record on 2 May 2026 is no surprise. Strokes, not flashes, are listed: with 1.49 strokes per flash, 3,195 strokes are about 2,150 flashes.
Years differ by a factor of four
From 130 strokes in 2025 to over 600 in 2020. Four years of fault records are a short sample of a noisy process, which is one reason the model and the record differ.
Faults follow the lightning, roughly
The towers with most strokes nearby are also among the most faulted, but not in proportion: footing resistance, height, arresters and terrain decide which strokes become faults. That is what the other pages model.