Decisions · Lightning climate

How much lightning does the line see?

Every design number on this site starts from two inputs: how often lightning strikes the ground near the line, and how strong the strokes are. Here is what the lightning-location system recorded around the SBSLM–SGKIL line from May 2019 to June 2026, and how it compares with the standard assumptions.

Where the strokes fell

local km, north up, zoomed to the recorded strokes · click a tower
negative strokepositive strokeline, every 10th tower labelledT16–T25 (this site's study section)

Peak current

recorded strokes against standard distributions
recordedCIGRE first negative (31 kA)log-normal 22 kA, σ 0.48

Strokes per year

Click a tower on the map for its numbers.

Along the line: strokes within 1 km and lightning faults 2022–2025

towers 1–118
strokes within 1 km (2019–2026)lightning faults attributed to the towerT16–T25
What to take away

Five lessons

A hotspot, not an average

The line-average ground flash density is about 4 flashes/km²/yr, but around T19–T28 it reaches 12–13. Every rate on this site uses the local value of each tower. A design based on the average would underestimate this section threefold.

Weaker strokes than the textbook

The median recorded peak is 22 kA against 31 kA in the CIGRE distribution. More weak strokes means more strokes inside the 5.7–17 kA window that can reach phase S, and fewer above the backflashover threshold.

The record misses what matters most

Detection efficiency is lowest for weak strokes, exactly those that cause shielding failures. A 10 kA stroke missing from the record on 2 May 2026 is no surprise. Strokes, not flashes, are listed: with 1.49 strokes per flash, 3,195 strokes are about 2,150 flashes.

Years differ by a factor of four

From 130 strokes in 2025 to over 600 in 2020. Four years of fault records are a short sample of a noisy process, which is one reason the model and the record differ.

Faults follow the lightning, roughly

The towers with most strokes nearby are also among the most faulted, but not in proportion: footing resistance, height, arresters and terrain decide which strokes become faults. That is what the other pages model.

Data
Vaisala FALLS cloud-to-ground strokes within the corridor buffer, 24 May 2019 – 23 June 2026 (7.08 years), 3,195 strokes; nearest tower and distance from the line database; lightning faults per tower 2022–2025 from the fault history (49 faults). Source: SBSLM_SGKIL_Model_Parameters.xlsx, sheets 2, 5 and 6. Positions are shown as local kilometres from the centroid of the line; absolute coordinates are not published. The record covers mainly the northern segment, about towers 16–77.